In close partnership with Rolla,TCS have developed the front access, high density, highly economic, MCCB  Q-System Switchboard. This switchboard is a dead-front design with overall doors to prevent unauthorised access to the outgoing devices. The switchboard is 2375mm high including 75mm plinth x 665mm deep as standard and a full height single column can accommodate 24 MCCBs of up to 250A plus 2x400A MCCBs. Cable ways can easily accommodate large outgoing cables and come in two sizes, 300mm wide for half columns and 550 wide for full columns.

This typical 4-column switchboard is 5.2M long, has a 2000A incomer
and includes the following facilities:
38 - 250A TPN MCCBs
6 - 400A TPN MCCBs
Metering on 20 outgoing ways
1 - 1250A Bus switch
1 - 1250A Auto Generator Incomer
6-stage, 300kVAr Automatic PFC
Top/bottom cable entry for outgoing ways.
 

We offer the following options and facilities:

  • IP42 Ingress protection
  • Top, bottom or special cable entry
  • Front cabling access
  • Separation: Form 4 Type 2
  • 660V Rating
  • Plain or tinned copper busbars
  • Door restraint integral in design of hinges.
  • Metering on any or all outgoing ways without increasing dimensions.
  • Available in a range of RAL or BS4800 colours.
  • All outgoing ways are connected using solid rigid copper connectors, and all spare ways can be equipped at a later date, or devices changed, with minimal plant disruption.
  • Main busbars rated either 2000A or 3200A
  • Short-circuit withstand strength of 50kA/3sec using ROLLA type tested KATTA busbar system.
  • 75mm RSC plinth as standard, other sizes available on request.
  • External covers are automatically earthed through design, without additional earth cables.
  • Typical final installed weight of 1 Tonne per column.