Horizontal Immersion Heated Hot Water (Flow) Boilers

Model No

Rating(kW)

Stages

Full load Current

Min Flow Rate

Dimensions(mm)

400V

GPM

L/S

L

W

H

HIHW 25

25

1

36.0

7.1

0.54

1525

635

810

HIHW 50

50

2

72.2

14.2

1.08

1525

635

810

HIHW 75

75

3

108.3

21.3

1.62

1525

635

810

HIHW 100

100

4

144.3

28.4

2.16

1525

635

810

HIHW 125

125

5

180.4

35.5

2.70

1525

765

1050

HIHW 150

150

6

216.5

42.6

3.24

1525

765

1050

HIHW 175

175

7

252.6

49.7

3.78

1525

765

1050

HIHW 200

200

8

288.7

56.8

4.32

1525

765

1050

HIHW 225

225

9

324.8

63.9

4.86

1525

865

1050

HIHW 250

250

5

360.9

71.0

5.40

1525

865

1050

HIHW 275

275

6

396.9

78.1

5.93

1525

865

1050

HIHW 300

300

6

433.0

85.2

6.47

1525

865

1050

HIHW 350

350

7

505.2

99.4

7.55

1985

940

1200

HIHW 400

400

8

577.4

113.6

8.63

1985

940

1200

HIHW 500

500

10

721.7

142.0

10.79

1985

940

1200

HIHW 600

600

6

866.1

170.4

12.95

2150

1120

1650

HIHW 700

700

7

1010.4

198.8

15.10

2150

1120

1650

HIHW 800

800

8

1154.7

227.2

17.26

3100

1475

2050

HIHW 1000

1000

10

1443.4

284.0

21.58

3100

1475

2050

HIHW 1250

1250

13

1804.3

355.0

27.0

3100

1475

2050

The current for voltages other than 400V = kW

 

Model No

BSP Connections

Nett Weight

Flow

Return

Safety

Drain

Empty

Filled

A

B

C

D

lbs

kg

lbs

kg

HIHW 25 to HIHW 100

2"

2"

1"

¾"

550

250

637

290

HIHW 125 to HIHW 200

2"

2"

1"

¾"

680

309

875

398

HIHW 225 to HIHW 300

3"

3"

1¼"

¾"

1049

477

1353

615

HIHW 350 to HIHW 500

3"

3"

1½"

¾"

1163

529

1601

728

HIHW 600 to HIHW 700

4"

4"

2"

¾"

1830

832

2609

1186

HIHW 800 to HIHW 1250

4"

4"

2½"

1"

2442

1110

3659

1663